- True
RMS
- A.C.
Measurement
- 3
Ammeters in one
- Remote
monitoring
- Large
LED Display
- Standard
96 X 96 case
- +/-
3 digits accuracy
|
| |
For
other panel meter products select your preference in
the menu on the right > |
| |
| The
Microsolve three phase Amp meter covers all the requirements
that you may have in an A.C. environment. This state
of the art instrument uses a 10 bit analogue to digital
microprocessor technology to bring you an inexpensive
yet reliable and accurate instrument. Designed using
the minimum of components for long term reliability,
the measuring algorithm takes approximately 400 readings
per second, yet the display is updated in such a manner
that the reading is comfortable on the eye. |
| |
This
instrument has been specifically designed for current
supply monitoring in diverse applications such as motor
panels, process control, temperature control, in fact
any application in which the current supply needs to
be monitored.
|
| |
The
input requires 3 star connected instrument type current
transformers (Class 1) with a secondary of 5 Amps. The
only requirements, is that the three current transformers
must be of the same ratio for correct readings on the
display. The display can be easily adjusted to accommodate
the ratio of the current transformer by simply adjusting
a 15 turn potentiometer on the main board. Access to
this potentiometer, requires the user to remove the
bezel and front plastic plate, and with an insulated
shaft mini screwdriver, rotate the potentiometer until
the desired current value is displayed. Setting the
decimal point is just as easy, simply move a jumper
to select the required position. |
|
|
Three
phase current monitoring
DPM-3AMA
|
| |
Supply
input |
110V,
230V, 400V, 525V 20% of nominal supply. Supply
less than 30% will cause display to flash "150".
|
Measurement
input |
0 to 5 Amp A.C..for each input. Star
connection via Class 1 type C.T.
Span adjustable from 1 to 999 via front
Panel adjusted potentiometer.
Decimal point selectable via front jumper
|
Accuracy |
+/- 2 digits across measurement range
|
Operating
Temperature |
-5
to 60 degrees centigrade
|
Relative
humidity |
Maximum
75% at 40 degrees Celsius |
|
|
|