Housed
Monitors
|
|
Housing: |
SABS with
11-Pin Plug-In Base |
Protection: |
1P30 |
Size: |
80x80x35mm
(Excluding pins) |
Supply
Voltage: |
12-24-48-110-220-380-525
VAC 12-24-48-110-220 VDC
Scale Accuracy: 5% |
Repeatability: |
1% |
Relay
Rating: |
10 Amp
Single change over at 220VAC
5 Amp Double change over at 220VAC |
Standared
Time Ranges: |
1 - 3 -10
- 30 - 60 - 90 -180 - 300 - 600 sec
30 - 60 -180 min |
Range
Accuracy |
+/- 5% |
Voltage
Limits |
+/- 15%
specified voltage |
Temperature
Limits |
-15 deg
C + 55 deg C |
Function |
Code |
Function
Drawing |
Connection
Diagram |
LIQUID
LEVEL CONTROLLER |
PLLP |

|

|
Operation
|
PLLP
- Liquid Level Controller (Filling & Emptying)
1. Filling Mode (No Link) On Power-up, Red LED is ON.
If liquid drops to Low level, Relay will be ON. When
liquid reaches Upper level, Relay will release. Unit
will remain in this position, or repeat operation as
levels move between the two set levels.
2. Emptying Mode (Link 8-9) As above, but in reverse
order. When liquid reaches Upper level, Relay is ON;
and Lower level Relay will be OFF. |
Function |
Code |
Function
Drawing |
Connection
Diagram |
MULTI
VOLTAGE COMPARATOR RELAY |
PVC |

|

|
Operation
|
PVC
- Multi-Voltage Comparator (Hysteresis Adj. 10-30%)
On Power-up, Red LED is ON. If voltage is below set-value,
the Relay will be OFF. If voltage is over set-value,
Relay will energize (Yellow LED ON), indicating that
the controller has tripped. The controller will maintain
this condition until applied voltage drops to hysteresis
setting.
Using Latch Function (Join 8-9)
If voltage exceeds set-value, Relay will energize (Yellow
LED ON), indicating that the controller has tripped.
The controller will remain in this condition irrespective
of voltage value. The controller will only reset by
removing power or latch 8-9. |
Function |
Code |
Function
Drawing |
Connection
Diagram |
SINGLE
PHASE COMPARATOR |
PSPU1 |

|

|
Operation
|
PSPU1
- Single Phase Window Detector
On Power-up, if voltage within set values, Yellow LED
is ON (Relay ON). If voltage exceeds Upper value, Red
LED is ON (Relay is OFF). If voltage drops below Lower
value, Green LED is ON (Relay is OFF). Relay is only
ON when Yellow LED is on. Link 8-9 As above, but if
voltage veers outside pre-set values, the unit will
latch in that condition. To release, remove power or
link.
Link 9-11 On Power-up irrespective of condition, unit
is ON for 10 sec. After this time, unit will function
as normal. |
Function |
Code |
Function
Drawing |
Connection
Diagram |
THREE
PHASE WINDOW COMPARATOR |
PSPU3 |

|

|
Operation
|
PSPU3
- Three phase window detector. Over and under voltage
protection. Can monitor on own supply.PSPU3 -3 Phase
Window Detector + Phase Sequence
Operation as above, but unit is able to monitor and
react to each phase
individually. Over the voltage detection, should any
phase goes out of sequence
Red Green LED will flash. |
Function |
Code |
Function
Drawing |
Connection
Diagram |
OVER
/ UNDER CURRENT RELAY |
PFP |

|

|
Operation
|
PFP
- Over and under current relay for AC/DC direct 1/5
amp shunt AC/DC. Compatible to C.T. |
Function |
Code |
Function
Drawing |
Connection
Diagram |
OVER
/ UNDER CURRENT WINDOW RELAY |
PCWD |

|

|
Operation
|
PCWD
- Over and under current window for AC/DC direct 1/5
amp shunt AC/DC. Compatible to C.T. |
Function |
Code |
Function
Drawing |
Connection
Diagram |
MOTOR
START PROTECTION RELAY |
PPST |

|

|
Operation
|
PPST
- Motor Start Protection Monitor
On 1~ start attempt, 1~ LED and 1-Hour timer will commence.
2nd start attempt will light 2nd LED and on 3~ start
attempt Lock-Out relay will energise (Red LED ON). To
reset, remove power or wait for 1-Hour. |
Function |
Code |
Function
Drawing |
Connection
Diagram |
STANDBY
GENERATOR SETS CONTROLLER |
PSA |

|

|
Operation
|
PSA
- Standby generator set controller. User selectable
number of starts (0-9). |
|
|
 |
|
 |
|
|